Beijing Zetron Technology Co., Ltd

info@bjzetron.com CN

Zetron BH-50 Gas Control Pane

The product has high stability. With high accuracy and high intelligence, the external control port is rich, and the user can freely choose the type of the connected transmitter and the access port.

Details

BH-50 Gas Control Panel-four Channel

The product has high stability. With high accuracy and high intelligence, the external control port is rich, and the user can freely choose the type of the connected transmitter and the access port.

This product is a single-channel / dual-channel / four-way (4-20) mA / RS485 transmitter signal input intelligent control system developed by the company. The product has high stability. High accuracy and high intelligence, the external control port is rich, the user can freely choose the type of the connected transmitter and the access port, and can perform on-site detection and alarm by simple setting. The system has integrated sound and light alarms and provides a relay normally open control terminal.
The system is widely used in applications where toxic and harmful gases need to be detected. When the index of a certain gas to be tested in the field exceeds or falls below the set standard, the system will perform a series of alarm actions, such as alarm, exhaust, tripping, etc.

Detection principle: Collect standard 4~20mA signal input or RS485 communication input (optional), analyze and display the current gas concentration of each channel, operate related alarm signals, and transmit the information to the computer through RS485 bus.


Tag: Gas control panel, Four Channel , Multi-gas channel gas controller, Dual-channel , Single channel gas control panel, Gas leakage on-site detection,  LPG detecter, Chlorine and combustible gases, Toxic and harmful gases , OEM/ODM service

Parameter

Product type BH-50 Gas controller
Channel Single channel,two channels,four channels
Power supply AC220V±10% 50Hz
Consumption ≦10W
Signal input 4~20mA and RS485
Single output two lines RS485(MODBUS)
Working temperature -10℃~50℃
Working humidity 0-95%RH (no dew)
Contact output Free contact output, max power 1kW
Installation method Wall-mounted
Dimensions 380x210x80mm(L×W×H)

Model Range Resolution L-alarm H-alarm
CO 0-1000ppm 1ppm 50ppm 150ppm
O2 0-30%vol 0.1%vol 19.5%vol 23.5%vol
H2 0-1000ppm 1ppm 50ppm 150ppm
H2S 0-100ppm 0.1ppm 10ppm 20ppm
CH4 0-100%LEL 1%lel 20%LEL 50%LEL
C2H4O 0-100ppm 1/0.1ppm 20ppm 50ppm
EX 0-100%LEL 1%lel/1%vol 20%LEL 50%LEL
C3H8 0-100%LEL 1%lel/1%vol 20%LEL 50%LEL
C2H5OH 0-100%LEL 1%lel/1%vol 20%LEL 50%LEL
NH3 0-100ppm 0.1/1ppm 20ppm 50ppm
CL2 0-20ppm 0.1ppm 5ppm 10ppm
O3 0-10ppm 0.1ppm 2ppm 5ppm
SO2 0-20ppm 0.1/1ppm 5ppm 10ppm
PH3 0-20ppm 0.1ppm 5ppm 10ppm
CO2 0-5000ppm 1ppm/0.1%vol 1000ppm 2000ppm
NO 0-250ppm 1ppm 50ppm 150ppm
NO2 0-20ppm 0.1ppm 5ppm 10ppm
HCN 0-50ppm 0.1/0.01ppm 10ppm 20ppm
HCL 0-20ppm 0.001/0.1ppm 5ppm 10ppm
CH2O 0-20ppm 1/0.1ppm 5ppm 10ppm
HF 0-100ppm 0.01/0.1ppm 2ppm 5ppm
C7H8/C8H10 0-20ppm 0.01/0.1ppm 5ppm 10ppm

Note: Not all gases and ranges are listed, if you need more information, please contact us.

Application

Applicable objects: The system supports input signals of various standard detectors, such as gas detectors: carbon monoxide, hydrogen sulfide, sulfur dioxide, hydrogen, ammonia, oxygen, chlorine, and combustible gases.

Video

Sorry  There is no "Application", you can view other services。

Product
selection

Here are all the products you want
Search for matching products

Search products

More products