Beijing Zetron Technology Co., Ltd

info@bjzetron.com CN

MS104K Liquefied Petroleum Natural Gas Analyzer

MS104K gas analyzer is possible to set whether to display the maximum value, minimum value, average value or not.

Details

MS104K Portable Natural Gas Leak Detector

Data recovery function; in case of mis-operation, it is possible to select partial or full recovery.

It is possible to set whether to display the maximum value, minimum value, average value or not. Standard USB charging port, with charging protection function, USB hot-plug supported,and the charging status instrument can work properly. 2100mA high capacity rechargeable polymer battery is adopted, so it is possible to work for a long period of time.

Gases to be detected
Range
Accurancy
Resolution
Response time T90
Methane ( CH4 )
0-100%Vol
<±3%(F.S)
0.1%Vol
≤10 seconds
Carbon monoxide ( CO )
0-100ppm
<±3%(F.S)
0.1ppm
≤25 seconds
Carbon dioxide ( CO2 )
0-100%Vol
<±3%(F.S)
0.01%Vol
≤30 seconds
Formaldehyde ( CH2O )
0-100ppm
<±3%(F.S)
0.01ppm
≤30 seconds
Chlorine gas ( CL2 )
0-10ppm
<±3%(F.S)
0.001ppm
≤30 seconds
Ammonia gas ( NH3 )
0-100ppm
<±3%(F.S)
0.01ppm
≤30 seconds
Helium gas ( He )
0-100%Vol
<±3%(F.S)
0.01%Vol
≤20 seconds
Argon gas ( Ar )
0-100%Vol
<±3%(F.S)
0.01%Vol
≤20 seconds


Parameter

Detection range

0 ~ 1, 10, 100, 1000, 5000, 50000, 100000ppm, 200 mg/L, 100%LEL, 

20%, 50%, 100%Vol, can be selected; and other ranges can be customized.

Detection principle

Electrochemical, catalytic combustion, infrared, thermal conductivity,

 PID photoionization, and so on, depending on the type of gas, range,

 field environment and user demand.

Sensor service life

Electrochemical principle: 2 ~ 3 years; Oxygen gas: 2 years or 6 years

 can be selected; infrared principle: 5 ~ 10 years;

Allowable error ≤±3% F.S (higher precision levels can be customized)
Response time T90≤30 seconds
Working environment Temperature: -40 ℃ ~ + 70 ℃, humidity: ≤10 ~ 95% RH
Sample gas temperature

-40 ℃ ~ + 70 ℃, and the optional configuration of high-temperatur

sampling and cooling filter handle will be possible to detect

the smoke gas at the temperature of 400 ℃ or higher.
Power supply 3.7VDC, 3000mA high capacity rechargeable polymer battery
Display mode 2.31-inch high-definition color screen
Data storage Standard configuration is the data storage capacity for 100, 000 entries
Protection level IP65
Explosion-proof type Intrinsically safe type
Explosion-proof mark Exia II CT4 Ga
Exterior dimensions 130×68×34mm (L×W×H)
Weight 200g
Standard accessories

Manual, qualification certificate, warranty card, USB charger (including

 the data cable), belt clip, colorful packaging box (optional high-grade aluminum instrument case)

Application

All the cases which requires the portable rapid detection of gas concentrations such as petroleum, chemical, pharmaceutical, environmental protection, combustion gas distribution, warehousing, smoke gas analysis, air governance, and so on.

Video

Product
selection

Here are all the products you want
Search for matching products

Search products

More products